Hochiki- FIRESWITCH 108 - 10AMP NAC BOOSTER

  HOCHIKI FDAS FIRESWITCH 108 - 10AMP NAC BOOSTER  

FEATURES

  • High-capacity NAC expansion for fire panels

  • This booster is designed to interface with 12 VDC or 24 VDC fire alarm control panels (FACPs) to expand notification appliance circuit (NAC) capacity—enabling additional horns/strobes or ADA-compliance devices.

  • Configurable outputs with multiple modes

  • The unit offers eight outputs (programmable as Class B or paired for Class A) and supports selectable output modes—Steady, Temporal Code 3, Strobe Synchronization, or Follower Mode (output mirrors input).

  • Fully supervised and network-ready

  • Each output is supervised for open/short/ground fault, the unit integrates LCD status display and Ethernet port for remote monitoring/programming, and supports ground-fault detection and form “C” relay trouble outputs.

  • Battery backup and power regulation

  • Includes internal battery charger, automatic switch-over to standby batteries, regulated 24 VDC output, and is capable of zero-voltage-drop switchover in an outage.

  • Synchronization and compatibility with major devices

  • Supports synchronization protocols for major brands (Gentex, System Sensor®, CooperWheelock®), enabling horn/strobe coordination, 2-wire horn/strobe mode, and CO Temporal Code 4 support.

SPECIFICATIONS

  • AC Input: 120 V AC, 60 Hz, 4.8 A max (as per spec sheet)

  • Output Voltage: 24 V DC regulated for NACs

  • Maximum Alarm Current (Total): 10 A

  • Maximum Stand-by Current (Without Battery): 7 A (without battery backup)

  • Maximum Current Per Output Channel: 2.5 A

  • Auxiliary Output: 1 A regulated 24 VDC (with battery backup)

  • Operating Temperature: 0 °C to +49 °C (32 °F to 120 °F)

  • Dimensions (H × W × D): 15.5″ × 12″ × 4.5″ (~393.7 mm × 304.8 mm × 114.3 mm)

  • Weight: ~12.4 lb (5.62 kg) net

  • Listings: UL 864, UL 2017, CAN/ULC-S527-99, FM, CSFM approved

  HOCHIKI FDAS HHLFR - LOW FREQUENCY HORN, 24VDC, WALL MOUNT  

FEATURES

  • High Performance Low Frequency Output

  • Produces a 520 Hz tone designed to meet NFPA 72 requirements for sleeping area notification.

  • Low Current Consumption

  • Optimized circuitry provides efficient operation while maintaining high sound output levels.

  • Multiple Tone and Volume Settings

  • Selectable sound patterns and volume levels allow flexibility for different environments.

  • Easy Installation and Wiring

  • Features universal mounting plate and quick-connect terminals for faster installation.

  • Aesthetically Designed Housing

  • Compact, modern housing with red finish blends with building interiors while meeting visibility requirements.

  • UL Listed for Fire Protection Use

  • Meets UL464 and NFPA 72 standards for audible notification appliances.

SPECIFICATIONS

  • Model: HHLFR

  • Type: Low Frequency Horn, Wall Mount

  • Operating Voltage: 16 – 33 VDC (nominal 24VDC)

  • Sound Output: Minimum 75 dBA @ 10 ft (520 Hz)

  • Current Draw: Up to 90 mA @ 24VDC (depending on setting)

  • Frequency Output: 520 Hz ± 10%

  • Synchronization: Compatible with Gentex sync protocols

  • Mounting: Standard 4” square or single-gang box

  • Housing Color: Red

  • Dimensions: 5.3” H x 4.6” W x 1.9” D

  • Operating Temperature: 32°F – 120°F (0°C – 49°C)

  • Humidity: Up to 90% RH non-condensing

  • Compliance: UL464, NFPA 72, ADA compliant

  HOCHIKI FDAS SPC-24 - BEAM DETECTOR  

FEATURES

  • Projected-beam detection for large open spaces

  • The SPC-24 uses separate emitter and receiver units to monitor a beam of light across distances up to ~328 ft (100 m) so it’s suitable for atria, high ceilings, warehouses, tunnels and other areas where spot detectors may be inefficient.

  • Microprocessor-based stability with automatic signal compensation

  • It features microprocessor control that stores the initial beam intensity, monitors variations, and includes automatic compensation for lens contamination or signal drift to maintain reliability over time.

  • Simple field alignment and configurable sensitivity

  • The unit provides signal-strength LEDs to assist installation alignment and supports three field-adjustable obscuration/sensitivity settings so it can be tuned for the specific area layout.

  • Dual-contact output for alarm and fault reporting

  • Provides Form A (alarm) and Form B (trouble) relay contacts for integration into fire panels and control systems.

  • Colour-coded units for ease of installation and service

  • Emitter and receiver units are colour coded (e.g., red & green) to avoid confusion during installation or servicing.

SPECIFICATIONS

  • Product Code: 0200‑03460

  • Operating Voltage: 19–33 VDC, nominal 24 VDC supply

  • Standby Current: ~200 µA (receiver); 50 µA (emitter)

  • Alarm / Trouble Current (receiver): ~20 mA each

  • Coverage Range: 32.8–328 ft beam span, covers 60 ft on-center

  • Dimensions: ~3.2″ W × 5.5″ H × 4.0″ D

  • Operating Temp: 14 °F–122 °F (–10 °C to 50 °C); UL-listed installation up to 100 °F

  • Humidity: Up to 95% RH (non-condensing)

  • Mounting: Wall mount or single-gang box

  • Certifications: UL 268 listed; California State Fire Marshal #7260‑0410:172

Inquire Now

a man riding a skateboard down the side of a ramp
a man riding a skateboard down the side of a ramp
Address

23 1st Ave. Brgy. Bagong Lipunan ng Crame, Cubao, Quezon City, 1111 Metro Manila, Philippines

Contacts

+632 8287 4114 | +632 8254 1594 +632 7720 1310 | + 632 8726 9129
inquiry@fastlink.ph | helpdesk@fastlink.ph

About Us

Our Solutions

Our Services

Contact Us