Hochiki- HCVX-2R 2 Zone Conventional Panel

  HOCHIKI FDAS HCVX-2R 2 ZONE CONVENTIONAL PANEL  

FEATURES

  • Compact Two-Zone Fire Protection

  • Ideal for small commercial or residential projects requiring basic but reliable fire detection capability.

  • High-Performance Power Supply

  • Includes a 5 A DC power source for NACs and detectors, ensuring sufficient drive capacity for multiple initiating devices.

  • Selectable NAC Synchronization

  • Supports selectable sync protocols (Gentex, Cooper, AMSECO) for proper visual and audible signaling control.

  • Easy Installation and Maintenance

  • Removable terminal blocks, large internal space for wiring, and field-configurable options simplify setup and service.

  • UL-Listed Reliability

  • Fully compliant with UL 864 10th Edition for dependable operation and safety assurance.

SPECIFICATIONS

  • Product Code: 0100‑19320 (2‑Zone, 120 VAC)

  • Zones: 2 initiating circuits, selectable fire/supervisory

  • Power Supply: 5 A DC, from a 120 VAC or optional 230 VAC input, rated for 4.0 A NAC

  • Backup Battery: Supports up to 12 Ah (maintains 24‑hour standby per EN54‑4)

  • NAC: Two circuits @ 2.5 A each, total 4.0 A

  • Other Outputs: Fire, supervisory, and system trouble relay contacts (30 V DC, 1 A)

  • Power Fault & Aux 24 V: Auxiliary output rated 0.3 A resettable fuse; low‑battery and power fault LEDs supported

  • NAC Wiring: Supports Class A/B wiring with polarity-sensitive appliances

  • User Interface: Simple 3-button programming with LED zone indicators and walk‑test mode

  • Dimensions: ~14.5″ × 12.2″ × 4.25″, red steel enclosure

  • Listings: UL 864 certified, EN54‑2/4 compliant

  HOCHIKI FDAS HCVX-8R - 8 ZONE CONVENTIONAL PANEL  

FEATURES

  • Comprehensive Multi-Zone Fire Protection

  • Provides eight fully supervised initiating zones configurable for fire or supervisory use, offering reliable detection coverage for large commercial and institutional facilities.

  • Flexible Notification Appliance Control

  • Equipped with two NAC outputs rated at 2.5A each (4A total), supporting multiple synchronization protocols such as Gentex, Wheelock, and AMSECO for seamless integration with horns and strobes.

  • Built-In 5A Power Supply with Battery Backup

  • Incorporates a robust 5-amp power supply and accommodates two 12V batteries (7Ah or 12Ah) for uninterrupted performance during AC power loss.

  • User-Friendly Operation and Maintenance

  • Includes intuitive LED indicators, one-man walk test functionality, and clear status displays for quick system verification and maintenance operations.

  • UL-Listed Reliability and Easy Installation

  • UL 864-listed design with detachable terminal blocks, selectable zone wiring (Style B/C), and modular board layout ensuring fast installation and long-term system reliability.

SPECIFICATIONS

  • Zones (Initiating Circuits): 8

  • Notification Appliance Circuits (NAC): 2 outputs; 2.5 A each; combined max 4.0 A

  • Power Supply Rating: 5 A

  • AC Input: 115 V AC or 230 V AC, 50/60 Hz (supervised)

  • Standby Battery: Accepts two 12 V batteries (7 Ah or 12 Ah) wired in series for 24 V DC system operation

  • Maximum Current Draw: Panel draws up to ~5.18 A in alarm condition (does not include NAC device load)

  • Wire Gauge Range for Field Terminals: 14–22 AWG for zone, NAC, AUX etc

  • Approvals: UL 864 listed

  • Configuration: Zones individually selectable as Fire or Supervisory; selectable zone wiring style (Style B / Style C)

  HOCHIKI FDAS HCA-RA REMOTE ANNUNCIATOR  

FEATURES

  • Compact Remote Display and Control Unit

  • Provides full system status and control for Hochiki HCA Series Fire Alarm Control Panels, ideal for remote monitoring locations.

  • Backlit LCD Display

  • Equipped with a 2-line, 16-character LCD for clear indication of alarms, troubles, supervisory, and system status.

  • Full Function Keypad

  • Includes control keys for Reset, Silence, Acknowledge, and Drill, mirroring main panel operation for convenient remote use.

  • LED Status Indicators

  • Displays Power, Alarm, Trouble, Supervisory, and AC Fail via dedicated LEDs for immediate status identification.

  • Supervised RS-485 Communication

  • Connects to the main panel using a supervised RS-485 communication bus for reliable data transfer.

SPECIFICATIONS

  • Compatible Panels: HCA Series Fire Alarm Control Panels

  • Display: 2-line, 16-character LCD

  • Communication: RS-485 supervised link

  • Control Buttons: Reset, Silence, Acknowledge, Drill

  • LED Indicators: Power, Alarm, Trouble, Supervisory, AC Fail

  • Power Input: 24VDC (supplied from main FACP)

  • Mounting: Surface or flush mount

  • Enclosure Color: Red

  • Dimensions: 5.7” W x 4.5” H x 1.5” D

  • Operating Temperature: 32°F – 120°F (0°C – 49°C)

  • Humidity: Up to 95% RH non-condensing

Inquire Now

a man riding a skateboard down the side of a ramp
a man riding a skateboard down the side of a ramp
Address

23 1st Ave. Brgy. Bagong Lipunan ng Crame, Cubao, Quezon City, 1111 Metro Manila, Philippines

Contacts

+632 8287 4114 | +632 8254 1594 +632 7720 1310 | + 632 8726 9129
inquiry@fastlink.ph | helpdesk@fastlink.ph

About Us

Our Solutions

Our Services

Contact Us