Honeywell- XLS4000 Series Fire Alarm Control Panel
HONEYWELL FDAS XLS4000 SERIES FIRE ALARM CONTROL PANEL
FEATURES
Scalable Addressable System with Modular Expansion
Supports up to 10 signaling line circuit (SLC) loops, each with up to 318 devices per loop for large‑scale installations.
Intuitive 10″ Full‑Color Touchscreen Network Control Display
High‑resolution 1024 × 600 touchscreen shows color‑coded system status, point details, and history with advanced filtering.
Connected Life Safety Services (CLSS) Integration
Offers remote monitoring, diagnostics, automated inspection reporting, and firmware updates via cloud platform.
Flexible Networked Annunciator Options (ACM‑30 & XLS‑NCD)
Support LED/action‑button configurable annunciators and touchscreen panels for centralized or distributed control.
Supports Smart & Self‑Test Detectors
Measures compatible with Honeywell’s self-test photo and heat detectors to reduce physical maintenance.
SPECIFICATIONS
Loops Supported: Up to 10 SLC loops, each up to 318 devices (e.g. up to 3,180 devices total)
Compatible Detectors: Fire‑Lite, CLIP, FlashScan, Smart, Self‑Test types
Control Display: XLS‑NCD Touchscreen, 1024 × 600 resolution, various user controls
Programming Logic: Up to 2,000 programmable logic zones, 32 custom action buttons
Event History: Up to 10,000 events stored, with 3,000 displayed
Network Capability: Standard and high‑speed network support available
User Access Controls: Up to 50 users across five access levels
Certifications: UL 864 10th Edition listed; NFPA compliant
HONEYWELL FDAS ES-200XP ADDRESSABLE FIRE ALARM CONTROL PANEL FACP BUILT-IN CELLULAR COMMUNICATOR
FEATURES
All‑In‑One Panel with Integrated 5 G LTE‑M Cellular Communicator
Built‑in dual‑SIM (AT&T/Verizon) CLSS Pathway Pro module provides secure cloud and central station communications.
Single SLC Loop Supporting 198 Devices
Handles up to 99 detectors and 99 modules per loop suited for small‑to‑mid installations.
Autoprogram/Offline Programming Mode
“Learn mode” automatically configures device addresses and allows USB upload/download using FS‑Tools software for efficient programming.
Four Independently Programmable NAC Circuits with Sync Options
Each NAC circuit can be Class A or B and synchronized with System Sensor, Gentex, or Wheelock devices; supports temporal, continuous, and march tone outputs.
Advanced Maintenance and Alarm Features
Includes detector sensitivity monitoring, maintenance alerts, alarm‑verification, pre‑signal, PAS sequencing, and one‑person walk test with log.
SPECIFICATIONS
Panel Models: ES‑200X, ES‑200XC, ES‑200XI, ES‑200XP (XP variant includes cellular comm)
Supported Devices: Up to 198 addressable devices (99 detectors, 99 modules) per loop
Communicators:
• IP/POTS (ES-200X/XC);
• Integrated 5G LTE‑M dual‑SIM (ES‑200XP)
Power Supply & Interface: Panel electronics and transformer in metal chassis; supports USB and Ethernet programming
NAC Outputs: Four Class A/B loops; total 2.5 A per NAC, max 2.7 A system shared
Relays: Two programmable Form‑C relays + one fixed trouble relay
Display: Integral 80-character LCD, real‑time clock/calendar
History Capacity: 1,000 event records
Protocols: LiteSpeed and CLIP
Certifications: UL 864 10th Edition Listed; NFPA 72 compliant
HONEYWELL FDAS ES-50XP ADDRESSABLE FIRE ALARM CONTROL PANEL BUILT-IN CELLULAR COMMUNICATOR
FEATURES
Intelligent Addressable Control
Supports up to 50 addressable devices per SLC loop, providing precise fire detection and easy pinpointing of alarm sources for faster emergency response.
Built-In Cellular Communicator
Includes an integrated LTE cellular module for primary or backup reporting, eliminating the need for separate communicators or landlines.
User-Friendly Interface
Equipped with a large backlit LCD display and intuitive keypad for easy programming, monitoring, and system management.
Advanced Event Logging and Diagnostics
Stores up to 1000 events in non-volatile memory for comprehensive review and troubleshooting.
Flexible System Configuration
Expandable with remote annunciators, NAC extenders, and auxiliary relays for customized fire alarm solutions.
UL Listed and NFPA 72 Compliant
Certified for life safety applications and compatible with Hochiki addressable devices.
SPECIFICATIONS
Model: ES-50XP
Addressable Devices Supported: Up to 50 devices on one SLC loop
Communication Module: Built-in CLSS Pathway Pro dual SIM 5G LTE-M (AT&T/Verizon) and IP path
NAC Circuits: Two independently programmable NACs (Class A or B) with strobe synchronization
Programming Interface: USB port + Ethernet for upload/download of programming, history and firmware updates
Display: Back-lit LCD, 80 characters, with multi-line annunciation and status indication
Listings: UL 864, 10th Edition; ETL; CSFM
Device Programming: Auto-programming (“learn mode”), error checking for duplicate addresses
Battery Support: Internal charger supports batteries (consult manual for sizing depending on load)