Honeywell- MS-5UD & MS-10UD Fire Alarm Control Panels
HONEYWELL FDAS MS-5UD & MS-10UD FIRE ALARM CONTROL PANELS
FEATURES
Built-in DACT for Remote Reporting
Includes integrated digital communicator/transmitter for central station or fire watch notification.
Upload/Download via PS‑Tools Software
Supports remote and local programming through upload/download with Honeywell’s PS‑Tools software (UD series).
Supports System Sensor i3 Detectors with Diagnostics
Monitors maintenance and freeze supervisory signals sent by i3 smoke detectors for reliable performance.
Four NAC Circuits with Drive Capabilities
Four Class B or optional Class A NAC circuits supported; each NAC programmable with temporal or steady tone.
80‑Character LCD and Full Control Keypad
Features a backlit alphanumeric display with function keys including silence, reset, drill, and acknowledge.
SPECIFICATIONS
Zones: 5 programmable conventional initiating zones (Style B IDC)
NAC Outputs: 4 Class B (optionally Class A) NACs, synchronized; supported drive current up to 2.5 A or 3 A depending on model
Power Supply Models:
FLPS‑7 power supply for 7.0 A output (e.g., MS‑5UD‑7C/UDE)
FLPS‑3 for 3.0 A output (e.g., MS‑5UD‑3(E))
Battery Capacity: Supports up to two 18 Ah batteries (larger requires BB‑55 enclosure)
Communicator: On-board DACT with two telephone line connections
User Interface: 80-character backlit LCD, keypad with silence, reset, lamp test, drill, and acknowledge
Relay Outputs: Up to 3 programmable Form‑C relays (Alarm, Supervisory, Trouble) rated 2 A @ 30 VDC or 0.5 A @ 30 VAC
Sync Output: TB2 remote sync output for external power supply synchronization (for FLPS‑3 based models)
Listings: UL Listed (File S624), FM Approved, CSFM, MEA approvals
HONEYWELL FDAS XLS140-2 FIRE ALARM CONTROL PANEL
FEATURES
Highly Scalable Modular System
Starts with one SLC loop and expandable up to two isolated loops (Class A, B, or X), supporting up to 318 devices per loop. Integration into campus networks with up to 200 nodes is seamless.
FlashScan® Ultra‑Fast Protocol
Polls up to 318 devices in under 2 seconds, and activates as many as 159 outputs in under 5 seconds for rapid response.
Multi-Mode Display and Annunciator Options
Offers built-in 80-character display, optional 640-character XLS‑NCA2 touchscreen, and support for printer, EIA‑232, RS‑485 annunciators, and digital voice systems.
Comprehensive Notification Circuitry
Includes four built-in NACs (1.5 A each), synchronized with System Sensor, Wheelock, or Gentex strobes for code-compliant operation.
Advanced Logic, Smoke Control & Messaging
Supports Boolean logic, PS sequencing, automatic time control programs, HVAC smoke control integration, and remote maintenance via VeriFire® Tools.
SPECIFICATIONS
SLC Capacity: 1 standard, expandable to 2 isolated loops (up to 318 devices each; up to 3,180 per network node)
Power: Integrated switch-mode PSU—6.0 A total output (shared)
Inputs/Outputs: Four NACs (1.5 A each), selectable synchronization, alarm/trouble/supervisory/security relays
Communications: Standard UDACT, IP, GSM (optional), network support via proprietary modules
Display: 80-character QWERTY keypad display; optional 640-character touchscreen
History Capacity: 800 events + 200 alarm-only events stored in non-volatile memory
Battery Support: 18 Ah to 200 Ah (float rate 27.6 VDC; external enclosure required if >25 Ah)
Certifications: UL 864 9th Ed, UL 1076, CSFM, MEA, EN54‑2/4, NFPA 72 compliant
HONEYWELL FDAS 6820EVS ADDRESSABLE FIRE ALARM CONTROL PANEL WITH EMERGENCY VOICE SYSTEM
FEATURES
Integrated Voice Evacuation Capability
Combines addressable fire control with emergency voice system (EVS) in one unit, supporting up to 16 built-in audio zones and 15 configurable voice messages (expandable to 32 zones).
Dual‑Path Communication Support
Includes built-in DACT for IP and POTS reporting, enhancing system reliability during network or phone line failure.
Scalable Device Capacity & Network Capability
Supports one SLC loop (~318 devices), expandable via additional loops or network nodes (up to 1,110 devices with SK protocol). Up to 17 panels may be networked.
SWIFT Wireless Detector Integration
Compatible with SWIFT wireless devices via optional gateway allowing easy wireless expansion.
Failover “Degraded Mode” Operation
Maintains evacuation voice and alarm sequences even if CPU board fails, ensuring minimal service interruption.
SPECIFICATIONS
SLC Loop: Built-in loop supports up to 159 detectors + 159 modules; expandable to 1,110 points (SK protocol)
Speaker Zones: 16 zones built-in, expandable to 32
Voice Messaging: Up to 15 recordable one-minute messages assignable per zone
Communications: Built-in DACT supports IP + POTS reporting
Networking: Supports up to 17 linked panels via copper or fiber
Interface: Dedicated EVS display panel with programmable controls
Certifications: UL Listed (Fire EVS, S2766), CSFM, FDNY COA #6249; compliant with NFPA Emergency Communication & Mass Notification standards